QUINT-PS-100-240AC/24DC/5
Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
Noise Immunity Test According to EN 61000-6-2 1
Electrostatic discharge (ESD)
EN 61000-4-2
Criterion B 2
Housing
Level 4
Air discharge 15 kV
Contact discharge 8 kV
Electromagnetic HF field
EN 61000-4-3
Criterion A 3
Housing Level 3
Frequency range 80...1000 MHz/1.4...2.0 GHz
Field strength 10 V/m
Fast transients (burst)
EN 61000-4-4
Input 4 kV (Inst. Class 4, asymmetrical: Cable to ground)
2 kV (Inst. Class 4, symmetrical: Cable to cable)
Output 0.5 kV (Level 1, asymmetrical: Cable to ground)
0.5 kV (Level 1, symmetrical: Cable to cable)
Signal 1 kV (Level 1, asymmetrical: Cable to ground)
Surge current load (surge)
EN 61000-4-5
Input 4 kV (Level 4, asymmetrical)
Output 2 kV (Level 3, asymmetrical)
Signal 1 kV (Level 2, asymmetrical)
Conducted interference
EN 61000-4-6
Input/output/signal Level 3, asymmetrical
Frequency range 0.15...80 MHz
Voltage 10 V
Voltage dips
EN 61000-4-11 Criterion B
Input Mains buffering > 20 ms
Noise Emission Test According to EN 61000-6-3
Noise emission of housing
EN 55011
(EN 55022) 4
Class B
Industrial and domestic applications
1
EN 61000 corresponds to IEC 61000
2
3
Criterion B:
Criterion A:
Temporary adverse effects on the operating behavior, which the device corrects automatically.
Normal operating behavior within the specified limits.
4
EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22
Structure
7
1
2
AC input
85...264 V AC input voltage,
45...65 Hz frequency
DC output
24 V DC output voltage (default),
can be set between 22.5 and 28.5 V DC
14
OK C
14 D
O
Ou K
ut
24
5A
14
14 D
OK
Ou
ut
24
5A
,5 -2 ju
8,5 st
10 ut
0-2
N 40
13
13
C
tp
D
4
DC
3
V
2
13
13
DC
OK
C
tp
DC
DC
22 Ad
AC Inp
L
V
OK
V
V
5
6
3 DC OK output active
4 DC OK output floating
5 Potentiometer (covered) 22.5...28.5 V DC
6 DC OK LED
7 Universal DIN rail adapter UTA 107
Block Diagram
1
L (+)
DC
O K
N (-)
Figure 1
100029_04_en
Operating elements
PE
Figure 2
Block diagram
DC OK
13
14
PHOENIX CONTACT
4